Model |
SUN-3.6K-SG05LP1-EU |
SUN-5K-SG05LP1-EU |
SUN-6K-SG05LP1-EU |
SUN-7K-SG05LP1-EU |
SUN-7.6K-SG05LP1-EU |
SUN-8K-SG05LP1-EU |
SUN-10K-SG05LP1-EU |
Battery Input Data |
|
Battery Type |
Lead-acid or Lithium-ion |
Battery Voltage Range(V) |
40-60 |
Max.Charging Current(A) |
90 |
120 |
135 |
175 |
190 |
190 |
210 |
Max.Discharging Current(A) |
90 |
120 |
135 |
175 |
190 |
190 |
210 |
Charging Strategy for Li-ion Battery |
Self-adaption to BMS |
Number of battery input |
1 |
PV String Input Data |
|
Max. PV Access Power (W)
|
7200 |
10000 |
12000 |
14000 |
15200 |
16000 |
20000 |
Max PV Input Power(W) |
5760 |
8000 |
9600 |
11200 |
12160 |
12800 |
16000 |
Max PV Input Voltage(V) |
500 |
Start-up Voltage(V) |
125 |
MPPT Voltage Range(V) |
150-425 |
Rated PV Input Voltage(V) |
370 |
Max Input Short-Circuit Current(A) |
17+17 |
34+34 |
Max Operating PV Input Current(A) |
13+13 |
26+26 |
No.of MPP Trackers/No.of String Per MPP Tracker |
2/1+1 |
2/2+2 |
AC Input/Output Data |
|
Rated AC Input/Output Active Power(W) |
3600 |
5000 |
6000 |
7000 |
7600 |
8000 |
10000 |
Max AC Input/Output Apparent Power (VA) |
3960 |
5500 |
6600 |
7700 |
8360 |
8800 |
11000 |
Peak Power (off-grid)(W) |
2 times of rated power,10s |
Rated AC Input/Output Current(A) |
16.4/15.7 |
22.7/21.7 |
27.3/26.1 |
31.9/30.5 |
34.5/33 |
36.4/34.8 |
45.5/43.5 |
Max AC Input/Output Current(A) |
18/17.2 |
25/23.9 |
30/28.7 |
35.0/33.5 |
38/36.3 |
40/38.3 |
50/47.9 |
Max Continuous AC Passthrough (grid to load)(A) |
35 |
40 |
50 |
Rated Input/Output Voltage/Range(V) |
220V/230 0.85Un-1.1Un |
Grid Connection Form |
L+N+PE |
Rated Input/Output Grid Frequency/Range |
50Hz/45Hz-55Hz 60Hz/55Hz-65Hz |
Power Factor Adjustment Range |
0.8 leading-0.8lagging |
Total Current Harmonic Distortion THDi |
<3% (of nominal power)
|
DC Injection Current |
<0.5%ln |
Efficiency |
|
Max Efficiency |
97.6%
|
Euro Efficiency |
96.5%
|
MPPT Efficiency |
>99% |
Equipment Protection |
|
Integrated
|
DC Reverse Polarity Protection, AC Output Overcurrent Protection, Thermal Protection, AC Output Overvoltage Protection, AC Output Short Circuit Protection, DC Component Monitoring, Arc Fault Circuit Interrupter (optional), Anti-islanding Protection, DC Switch, Insulation Impedance Detection, Residual Current Detection |
Surge Protection Level |
TYPE II(DC),TYPE II(AC) |
Interface |
|
Communication Interface |
RS485/RS232/CAN |
Monitor Mode
|
GPRS/WIFI/Bluetooth/4G/LAN(optional) |
General Data |
|
Operating Temperature Range |
-40 to +60℃, >45℃ Derating
|
Permissible Ambient Humidity |
0~100% |
Permissible Altitude |
2000m |
Noise |
<30 dB(A) |
Ingress Protection(IP) Rating |
IP 65 |
Inverter Topology |
Non-Isolated |
Over Voltage Category |
OVC II(DC),OVC III(AC) |
Cabinet size(W*H*D)[mm] |
330×580×232 (Excluding Connectors and Brackets) |
Weight[kg] |
24.9 |
Warranty |
5 Years/10 Years the Warranty Period Depends the Final Installation Site of Inverter, More Info Please Refer to Warranty Policy |
Type Of Cooling |
Intelligent air cooling |
Grid Regulation |
IEC 61727,IEC 62116,CEI 0-21,EN 50549,NRS 097,RD 140,UNE 217002,OVE-Richtlinie R25,G98,G99,VDE-AR-N 4105 |
Safety EMC/Standard |
IEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2 |