| Model | SUN-7.6K-SG02LP1-EU-AM2 | SUN-8K-SG02LP1-EU-AM2 | SUN-10K-SG02LP1-EU-AM3 | SUN-12K-SG02LP1-EU-AM3 |
| Battery Input Data | ||||
| Battery Type | Lead-acid or Lithium-ion | |||
| Battery Voltage Range(V) | 40-60 | |||
| Max.Charging Current(A) | 190 | 190 | 220 | 250 |
| Max.Discharging Current(A) | 190 | 190 | 220 | 250 |
| Charging Strategy for Li-ion Battery | Self-adaption to BMS | |||
| Number of battery input | 1 | |||
| PV String Input Data | ||||
|
Max. PV Access Power (W)
|
15200 | 16000 | 20000 | 24000 |
| Max DC Input Power(W) | 12160 | 12800 | 16000 | 19200 |
| Max DC Input Voltage(V) | 500 | |||
| Start-up Voltage(V) | 125 | |||
| MPPT Voltage Range(V) | 150-425 | |||
| Rated DC Input Voltage(V) | 370 | |||
| Max. Operating PV Input Current (A) | 26+26 | 26+26+26 | ||
| Max. Input Short-Circuit Current (A) | 44+44 | 44+44+44 | ||
| No.of MPP Trackers/No.of String Per MPP Tracker | 2/2+2 | 3/2+2+2 | ||
| AC Input/Output Data | ||||
| Rated AC Input/Output Active Power(W) | 7600 | 8000 | 10000 | 12000 |
| Max AC Input/Output Apparent Power (VA) | 8360 | 8800 | 11000 | 13200 |
| Peak Power (off-grid)(W) | 2 times of rated power,10s | |||
| Rated AC Input/Output Current(A) | 34.6/33.1 | 36.4/34.8 | 45.5/43.5 | 54.6/52.2 |
| Max AC Input/Output Current(A) | 34.6/33.1 | 36.4/34.8 | 45.5/43.5 | 54.6/52.2 |
| Max Continuous AC Passthrough (grid to load)(A) | 50 | 60 | ||
| Power Factor Adjustment Range | 0.8 leading to 0.8 lagging | |||
| Rated Input/Output Voltage/Range (V) | 220/230 0.85Un-1.1Un | |||
| Rated Input/Output Grid Frequency/Range(Hz) | 50/45-55, 60/55-65 | |||
| Grid Connection Form | L+N+PE | |||
| Total Current Harmonic Distortion THDi | <3% (of nominal power) | |||
| DC Injection Current | <0.5%ln | |||
| Efficiency | ||||
| Max Efficiency | 97.6% | |||
| Euro Efficiency | 96.5% | |||
| MPPT Efficiency | >99% | |||
| Equipment Protection | ||||
|
Integrated
|
DC Reverse Polarity Protection, AC Output Overcurrent Protection, Thermal Protection, AC Output Overvoltage Protection, AC Output Short Circuit Protection, DC Component Monitoring, Arc Fault Circuit Interrupter (optional), Anti-islanding Protection, DC Switch, Insulation Impedance Detection, Residual Current Detection
|
|||
| Surge Protection Level | TYPE II(DC),TYPE II(AC) | |||
| Interface | ||||
| Communication Interface | RS485/RS232/CAN | |||
|
Monitor Mode
|
GPRS/WIFI/Bluetooth/4G/LAN(optional) | |||
| General Data | ||||
| Operating Temperature Range |
-40 to +60℃, >45℃ Derating
|
|||
| Permissible Ambient Humidity | 0~100% | |||
| Permissible Altitude | 2000m | |||
| Noise | <45 | |||
| Ingress Protection(IP) Rating | IP 65 | |||
| Inverter Topology | Non-Isolated | |||
| Over Voltage Category | OVC II(DC),OVC IV(AC) | |||
| Cabinet size(W*H*D)[mm] | 420×670×233(Excluding connectors and brackets) | |||
| Weight[kg] | 35.6 | |||
| Warranty | 5 Years/10 Years the Warranty Period Depends the Final Installation Site of Inverter, More Info Please Refer to Warranty Policy |
|||
| Type Of Cooling | Intelligent air cooling | |||
| Grid Regulation | VDE4105, IEC61727/62116, VDE0126, AS4777.2, CEI 0 21, EN50549-1, G98, G99, C10-11, UNE217002, NBR16149/NBR16150 |
|||
| Safety EMC/Standard | IEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2 | |||
Copyright@ 2024.Ningbo Deye Inverter Technology Co.,Ltd. All rights reserved. Solar Inverter Manufacturer