Modelo |
SUN-3K-SG05 LP3-EU-SM2 |
SUN-4K-SG05 LP3-EU-SM2 |
SUN-5K-SG05 LP3-EU-SM2 |
SUN-6K-SG05 LP3-EU-SM2 |
SUN-8K-SG05 LP3-EU-SM2 |
SUN-10K-SG05 LP3-EU-SM2 |
SUN-12K-SG05 LP3-EU-SM2 |
Battery Input Data |
|
Battery Type |
Lead-acid or Lithium-ion |
Battery Voltage Range (V) |
40-60 |
Max. Charging Current (A) |
70 |
95 |
120 |
135 |
190 |
210 |
240 |
Max. Discharging Current (A) |
70 |
95 |
120 |
135 |
190 |
210 |
240 |
Charging Strategy forLi-ion Battery |
Self-adaption to BMS |
Number of Battery Input |
1 |
PV String Input Data |
|
Max. PV Access Power (W)
|
6000 |
8000 |
10000 |
12000 |
16000 |
20000 |
24000 |
Max. PV Input Power (W) |
4500 |
6000 |
7500 |
9000 |
12000 |
15000 |
18000 |
Max. PV Input Voltage (V) |
800 |
Start-upVoltage (V) |
160 |
MPPT Voltage Range (V) |
200-650 |
Rated PV Input Voltage (V) |
550 |
Max. Operating PV Input Current (A) |
20+20 |
26+26 |
Max. Input Short-Circuit Current (A) |
30+30 |
39+39 |
No. of MPP Trackers/No. of Strings MPP Tracker |
2/1+1 |
2/2+2 |
AC Input/Output Data |
|
Rated AC Input/Output Active Power (W) |
3000 |
4000 |
5000 |
6000 |
8000 |
10000 |
12000 |
Max. AC Input/Output Apparent Power (VA) |
3300 |
4400 |
5500 |
6600 |
8800 |
11000 |
13200 |
Rated AC Input/Output Current (A) |
4.6/4.4 |
6.1/5.8 |
7.6/7.3 |
9.1/8.7 |
12.2/11.6 |
15.2/14.5 |
18.2/17.4 |
Max. AC Input/Output Current (A) |
5/4.8 |
6.7/6.4 |
8.4/8 |
10/9.6 |
13.4/12.8 |
16.7/16 |
20/19.2 |
Max. Continuous AC Passthrough (grid to load) (A) |
45 |
Peak Power (off-grid) (W) |
2 times of rated power, 10s |
Power Factor Adjustment Range |
0.8 leading to 0.8 lagging |
Rated Input/Output Voltage/Range (V) |
220/380V, 230/400V 0.85Un-1.1Un |
Rated Input/Output Grid Frequency/Range(Hz) |
50/45-55, 60/55-65 |
Grid Connection Form |
3L+N+PE |
Total Current Harmonic Distortion THDi |
<3% (of nominal power) |
DC Injection Current |
<0.5% In |
Efficiency |
Max. Efficiency |
97.6% |
Euro Efficiency |
97.0% |
MPPTEfficiency |
>99% |
Equipment Protection |
Integrated |
DC Reverse Polarity Protection, AC Output Overcurrent Protection, Thermal Protection, AC Output Overvoltage Protection, AC Output Short Circuit Protection, DC Component Monitoring, Arc Fault Circuit Interrupter (optional), Anti-islanding Protection, DC Switch, Insulation Impedance Detection, Residual Current Detection
|
Surge Protection Level |
TYPE II(DC),TYPE II(AC) |
Interface |
Communication Interface |
RS485/RS232/CAN |
Monitor Mode |
GPRS/WIFI/Bluetooth/4G/LAN(optional) |
General Data |
Operating Temperature Range (℃) |
-40 to +60℃, >45℃ Derating |
Permissible Ambient Humidity |
0-100% |
Permissible Altitude |
3000m |
Noise (dB) |
≤55 |
Ingress Protection(IP) Rating |
IP 65 |
Inverter Topology |
Non-Isolated |
Over Voltage Category |
OVC II(DC), OVC III(AC) |
Cabinet Size (WxHxD mm) |
386×660×250 (Excluding Connectors and Brackets) |
Weight (kg) |
35.2 |
Type of Cooling |
Intelligent Air Cooling |
Warranty |
5 Years/10 Years the Warranty Period Depends the Final Installation Site of Inverter, More Info Please Refer to Warranty Policy |
Grid Regulation |
IEC 61727, IEC 62116,CEI 0-21, EN 50549, NRS 097, RD 140, UNE 217002, OVE-Richtlinie R25,G98, G99,VDE-AR-N 4105 |
Safety / EMC Standard |
IEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2 |